Features
• IR-detection (obscuration)
• 300 mm proble lenght
• Outputs
Relay SPDT 1A@24Vdc, 120 Vac
Analogue2-10 Vdc
• Analogue output status levels
< 2 VdcSensor fault
< 3-7 VdcNormal operation
< 7-9 VdcOptics require cleaning
> 9,5 Vdc Smoke alarm
• The analogue output signal 2-10 Vdc can transmit
smoke or service alarm (dirt level) to BEMS system
• Relay output for closing fan/damper motor
• Damped or undamper output (jumper selection)
• Manual or auto reset (jumper selection)
• Reset button in front of enclosure
• Power supply 24 Vac/dc
• Early warning of smoke and fire
• Sensing smoke directly in the duct
Without help of built-in fan in the detector –
No use of sampling tubes
A True Duct Smoke Detector ! ! !